1. Configure Transmitter Span (LRV / URV)
2. Bidirectional Linear Scaling
Current
12 mA
Process
5 bar
% of Span
50%
Signal diagnostic: Normal 4–20 mA linear operating range
5-Point Calibration Check Table
Reference values for field commissioning and multi-point linearity verification
| Span % | Expected mA | Process Value (bar) |
|---|---|---|
| 0% | 4.00 mA | 0 bar |
| 25% | 8.00 mA | 2.5 bar |
| 50% | 12.00 mA | 5 bar |
| 75% | 16.00 mA | 7.5 bar |
| 100% | 20.00 mA | 10 bar |
Max Loop Load Resistance Calculator
R_max = (V_supply − V_min) / 0.020 A
Maximum Total Loop Resistance (PLC + Cable)
6 Ω
Standard PLC analog input cards typically present 250 Ω. Exceeding R_max causes voltage starvation and signal clipping near 20 mA.
4–20 mA / RS-485
Industrial Pressure Transmitters
Wide 9–32 VDC loop supply, ±0.25%FS accuracy options, and IP67/IP68 sealing.
Browse transmittersHydrostatic Level
Level Transmitters
Two-wire 4-20mA submersible level transmitters for tanks, deep wells, and water plants.
Browse level sensorsCompanion Tool
Pressure Unit Converter
Instant conversion across bar, MPa, kPa, PSI, mH2O, mbar, and 4 more units.
Open converter4-20mA Instrumentation Loop FAQ
What is the formula to convert 4-20mA current to an engineering pressure value?
For a linear transmitter with Lower Range Value (LRV) and Upper Range Value (URV), Process Value = LRV + ((I_mA - 4) / 16) × (URV - LRV). Conversely, Current (mA) = 4 + 16 × ((Process Value - LRV) / (URV - LRV)).
Why do industrial pressure transmitters use 4-20mA instead of 0-20mA?
The 4 mA live zero allows a PLC or controller to distinguish a true zero pressure reading (4 mA) from a broken wire, blown fuse, or disconnected sensor (0 mA). It also provides enough baseline current to power two-wire transmitters over long cable runs.
How do you calculate the maximum loop resistance for a 24VDC 4-20mA transmitter?
Use R_max (Ω) = (V_supply - V_min) / 0.020 A. For a typical 24 VDC power supply and a transmitter requiring at least 12 VDC minimum operating voltage, R_max = (24 - 12) / 0.020 = 600 Ω (including PLC input resistor and cable resistance).
What does a reading below 3.8 mA or above 20.5 mA indicate?
Per NAMUR NE43 diagnostics, readings below 3.6 mA or above 21 mA indicate sensor failure, wiring open/short circuit, or severe over-range condition rather than normal process variation.